Room nameDiscipline SelectionSubject MarkNotes
RoofHVACAC-1

Condensate line is broken. Piping under roof exists, but there is no sign it connects to the rooftop unit unless it is within the curb. No roof penetration.)

RoofHVACAC-2

Condensate line is broken. Piping under roof exists, but there is no sign it connects to the rooftop unit unless it is within the curb. No roof penetration.

RoofHVACAC-3

Condensate drain penetrates roof and goes down into space (back room).

RoofHVACAC-4

Condensate line is broken. Piping under roof exists, but there is no sign it connects to the rooftop unit unless it is within the curb.

RoofHVACAC-5

Condensate line is broken. Piping under roof exists, but there is no sign it connects to the rooftop unit unless it is within the curb. (No rooftop penetration.)

RoofHVACEF-1

Serves restrooms.

RoofHVACEF-2

Adjacent to AC-5.
Centri Master
Model: PV100E3
1/4 hp
115V
Serves Janitor?s Closet. More than 10 feet away from rooftop unit intake.

RoofHVACAC-6

Condensate line is broken. Piping under roof exists, but there is no sign it connects to the rooftop unit unless it is within the curb.

RoofHVACAC-7

Condensate drain penetrates roof and goes down into space (back room).

Back RoomHVACAC-7

Bottom of the supply air diffuser at 16?6?. Bottom of the return air duct at 17?8?.

Back RoomHVACAC-6

Bottom of the supply diffuser at 18?1?. Bottom of the return air duct at 19?3?.

Janitor’s ClosetHVACEF-2
Sales AreaHVACAC-5

Thermostat in rear corner of sales area.
Bottom of supply air duct at 19?7?. Bottom of return air duct at 17?6?. Return air goes through wall to new office fitting room space.

Sales AreaHVACAC-4

Active. (76 degrees.)
Thermostat on back of fifth right wooden partition. Will be demolished. Will need to specify relocation.
Remote test switch location on fourth column (from storefront).
Bottom of diffuser at 17?8?. Bottom of return air duct at 18?10?.

Sales AreaHVACAC-3

This thermostat is not powered.
Thermostat on third right wooden partition. Will be demolished. Will need to specify relocation.
Remote test switch location on back left of first (central) wooden partition that will be demolished. Will need to specify relocation.
Bottom of diffuser at 16?9?. Bottom of return air duct at 17?11?.

Sales AreaHVACAC-2

Thermostat on second right wooden partition. Will be demolished. Will need to specify relocation.
Remote test switch location on back left of first (central) wooden partition that will be demolished. Will need to specify relocation.
Bottom of diffuser at 16?4?. Bottom of return air duct at 17?7?.

Sales AreaHVACAC-1

Thermostat on first right wooden partition. Will be demolished. Will need to specify relocation.
Remote test switch location on front left of first (central) wooden partition that will be demolished. Will need to specify relocation.
Bottom of diffuser at 15?9?. Bottom of return air duct at 17?1?.